====Importing Data Bindings==== The fastest way to begin //importing// data bindings is to //export// your existing ones. This will then include each of the columns you need to import data back into your ARDI system. ===File Structure=== The data binding import file is a CSV (comma-delimited) file containing one row of data for each property you want to link to live data. ===Columns=== Several columns are required.... ^Column Name^Meaning^ |ERN|The Equipment Resource Number for your asset. If you don't use ERNs, leave this column blank.| |Name|The human-readable name for your asset. If you've supplied an ERN, this name isn't required (although the column itself still is).| |Type|The type of data binding (Property or Alert)| |Property/Name|The name of the property or the alert| |Node/ID|The name of the node, or ID number of the alert. This can usually be left blank, but the column is required| |Actual Live Source|The data-source for your live data| |Actual Live Address|The address to bind the property or alert to| |Actual Live Transform|The transformation to apply to the incoming data (often left blank)| And for each [[contexts|context]], you'll need to repeat those last three columns. At a minimum. you'll need the values below. |Actual History Source|The data-source for your live data| |Actual History Address|The address to bind the property or alert to| |Actual History Transform|The transformation to apply to the incoming data (often left blank)| ===Rows=== Below is an example linking the an oven temperature to a point found in OSI Pi. {{ioimportexample.png}} This row tells ARDI that we want to change the data bindings for the **Temperature** **Property** of the asset with the ERN **ABC-001**. We want both the live value //and// this history to come from the **PI Server**, at address **Ovens\001\Temperature**.